
I
d
controllers keep the motor flux constant using the output voltage, and adjust the matching
current component I
q
in the motor.
Settings that are required
Restart quick commissioning and select the vector control in quick commissioning.
Quick commissioning (Page 106)
In order to achieve a satisfactory control response, as a minimum you must set the partial
functions – shown with gray background in the diagram above – to match your particular
application:
• Motor and current model: In the quick commissioning, correctly set the motor data on the
rating plate corresponding to the connection type (Y/Δ), and carry out the motor data
identification routine at standstill.
• Speed limits and torque limits: In the quick commissioning, set the maximum speed
(p1082) and current limit (p0640) to match your particular application. When exiting quick
commissioning, the converter calculates the torque and power limits corresponding to the
current limit. The actual torque limits are obtained from the converted current and power
limits and the set torque limits.
• Speed controller: Start the rotating measurement of the motor data identification. You must
manually optimize the controller if the rotating measurement is not possible.
WARNING
The load falls due to incorrect closed-loop control settings
For encoderless vector control, the converter calculates the actual speed based on an electric
motor model. In applications with pulling loads - e.g. hoisting gear, lifting tables or vertical
conveyors - an incorrectly set motor model or other incorrect settings can mean that the load
falls. A falling load can result in death or serious injury.
• Correctly set the motor data during the quick commissioning.
• Carry out the motor data identification.
• Correctly set the "Motor holding brake" function.
Motor holding brake (Page 230)
• For pulling loads, carefully comply with the recommended settings for vector control.
8.19.2.2
Optimizing the closed-loop speed controller
Optimum control response - post optimization not required
Preconditions for assessing the controller response:
• The moment of inertia of the load is constant and does not depend on the speed
• The converter does not reach the set torque limits during acceleration
• You operate the motor in the range 40 % … 60 % of its rated speed
Advanced commissioning
8.19 Motor control
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
297