When using the control mode "U/f control" (p1300 < 10), the "Blocking protection" function
becomes active when the current limit is reached.
Setting pump monitoring
1. Set p2193 = 4.
2. The converter sets the monitoring as shown.
,ISUWKHQS U
,ISุUWKHQS SbUSP
6SHHG>USP@
/HDNDJH
'U\UXQQLQJSURWHFWLRQ
RUWRUQEHOW
S SbUSP
%ORFNHG
S SbUSP
S U
7RUTXH>1P@
S
U
S U
S SS
S U
S U
Figure 8-75
Default settings for pumps
3. The converter sets monitoring response p2181 = 7
4. If necessary, adjust the speed thresholds p2182 … p2184.
5. If necessary, adjust the torque threshold for each speed.
The converter displays the current torque in r0031.
You have now set monitoring.
❒
Advanced commissioning
8.27 Monitoring the driven load
Distributed converter for SIMOGEAR geared motors
334
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL