6. The converter transfers the firmware from the memory card into its memory.
The transfer takes between 5 and 10 minutes.
While data is being transferred, the LED RDY on the converter stays red. The BF LED flashes
orange with a variable frequency.
9
9
5'<
%)
%)
5'<
PLQ
7. Once the transfer is completed, the RDY and BF LEDs flash slowly red (0.5 Hz).
Note
Damaged firmware due to a supply voltage interruption during transfer
If the power supply fails during the transfer, this can damage the converter's firmware.
• Do not switch off the converter's supply voltage while the transfer is running.
8. Switch off the 24 V or the 400 V supply voltage of the converter.
9
9. Remove the Power Module.
10.Withdraw the card with the firmware from the Power Module.
Corrective maintenance
10.4 Firmware upgrade and downgrade
Distributed converter for SIMOGEAR geared motors
384
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL