• IND, bit 0 … 7 (page index): = 0 hex (offset 0 corresponds to 0 hex)
• PWE1, Bit 0 … 15: = 2D2 hex (722 = 2D2 hex)
• PWE2, Bit 10 … 15: = 3F hex (drive object - for SINAMICS G120, always 63 = 3f hex)
• PWE2, Bit 0 … 9: = 2 hex (Index of Parameter (DI 2 = 2))
3DUDPHWHUFKDQQHO
3:(KLJKUGZRUG
3:(ORZWKZRUG
,1'QGZRUG
3DJHLQGH[
3DUDPHWHUQXPEHU
6XELQGH[
3DUDPHWHUYDOXH
3.(VWZRUG
'ULYH2EMHFW
,QGH[
$.
Figure 8-14
Parameter channel to assign digital input 2 with ON/OFF1
Function description
AK: Request and response ID
Table 8-28
Request identifiers, control → converter
AK
Description
Response identifier
positive
nega‐
tive
0
No request
0
7 / 8
1
Request parameter value
1 / 2
7 / 8
2
Change parameter value (word)
1
7 / 8
3
Change parameter value (double word)
2
7 / 8
4
Request descriptive element
1)
3
7 / 8
6
2)
Request parameter value (field)
1)
4 / 5
7 / 8
7
2)
Change parameter value (field, word)
1)
4
7 / 8
8
2)
Change parameter value (field, double word)
1)
5
7 / 8
9
Request number of field elements
6
7 / 8
1)
The required element of the parameter is specified in IND (2nd word).
2)
The following request IDs are identical: 1 ≡ 6, 2 ≡ 7 and 3 ≡ 8.
We recommend that you use identifiers 6, 7 and 8.
Table 8-29
Response identifiers, converter → control
AK
Description
0
No response
1
Transfer parameter value (word)
2
Transfer parameter value (double word)
3
Transfer descriptive element
1)
4
Transfer parameter value (field, word)
2)
5
Transfer parameter value (field, double word)
2)
6
Transfer number of field elements
Advanced commissioning
8.6 Drive control via PROFIBUS or PROFINET
Distributed converter for SIMOGEAR geared motors
198