Accessing the DIP switches
DANGER
Dangerous voltages and currents are present in the active converter
When power is applied to the converter, even when it is not active, dangerous levels of voltage
and current are present in the system.
Before attempting the removal of any components of the system the following steps should be
taken to ensure that the system is completely safe:
1. Ensure that the converter is not running, if so, the converter must be stopped.
2. Disconnect all mains power supplies to the system. If an external 24 V supply is connected
to the system, then this does not have to be disconnected.
3. Wait 5 minutes to allow all the residual current and voltages to dissipate fully.
Generally the G110M system is delivered fully assembled on a motor which prohibits easy access
to the DIP switches. To access the DIP switches it is necessary to remove the Power Module; this
action is illustrated in the figure below.
3RZHU0RGXOH
7HUPLQDOKRXVLQJ
',3VZLWFKHV
Figure 5-6
Removing the Power Module
Description of the DIP switches functions
When the DIP switches are in the OFF position, the value of the function is defined by the default
value of the parameter. If the DIP switch is activated for a specific function, then the parameters
for that function cannot be modified by manually editing the parameter value, i.e. ready-only.
Commissioning
5.4 Quick commissioning
Distributed converter for SIMOGEAR geared motors
110
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL