Parameter
Parameter for Vdc_max control
The parameters differ depending on the motor control mode.
Table 8-74
Parameters for U/f control
Parameter
Description
Factory setting
p0210
Device supply voltage
400 V
p1280[D]
Vdc controller configuration (U/f)
1
r1282
Vdc_max controller switch-on level (U/f)
- V
p1283[0…n]
Vdc_max controller, dynamic factor (U/f)
100%
p1294
Vdc_max controller automatic ON level detection (U/f)
0
Table 8-75
Parameter for vector control
Parameter
Description
Factory setting
p0210
Device supply voltage
400 V
p1240[0…n]
Vdc controller configuration (vector control)
1
r1242
Vdc_max controller switch-in level
- V
p1243[0…n]
Vdc_max controller, dynamic factor
100%
p1254
Vdc_max controller automatic ON level detection
0
For additional information about this function, see the List Manual (function diagrams 6320 and
6220).
Manuals for your converter (Page 415)
Advanced commissioning
8.26 Motor and converter protection by limiting the voltage
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
329