Table 8-6
Additional settings for parameter p0756
0:
Unipolar voltage input
0 V ... +10 V
1:
Unipolar voltage input with monitoring
+2 V ... +10 V
2:
Unipolar current input
0 mA ... +20 mA
3:
Unipolar current input with monitoring
+4 mA ... +20 mA
9:
Unipolar voltage input
0 V ... +3 V
Defining the function of an analog input
You define the analog input function by connecting a connector input of your choice with
parameter p0755. Parameter p0755 is assigned to the corresponding analog input via its index,
i.e. parameter p0755[0] is assigned to analog input 0.
Parameters
Table 8-7
Connector inputs (CI) of the converter (selection)
Parameter
Description
Factory setting
p1070[C]
CI: Main setpoint
0
p1075[C]
CI: Supplementary setpoint
0
p1503[C]
CI: Torque setpoint
0
p1511[C]
CI: Supplementary torque 1
0
p1522[C]
CI: Torque limit, upper
1520
p2253[C]
CI: Technology controller setpoint 1
0
p2264[C]
CI: Technology controller actual value
0
A complete list of connector inputs is provided in the parameter list.
Further information
Signal smoothing
When required, you can smooth the signal, which you read-in via an analog input, using
parameter p0753.
Additional information is provided in the parameter list and in function diagram 2251.
Manuals and technical support (Page 415)
Advanced commissioning
8.4 Adapt the default setting of the inputs and outputs