• IND, bit 0 … 7 (page index): = 90 hex (offset 6000 corresponds to 90 hex)
• Because you want to read the parameter value, words 3 and 4 in the parameter channel for
requesting the parameter value are irrelevant. They should be assigned a value of 0, for
example.
3DUDPHWHUFKDQQHO
3:(KLJKUGZRUG
3:(ORZWKZRUG
,1'QGZRUG
3DJHLQGH[
3DUDPHWHUQXPEHU
6XELQGH[
3DUDPHWHUYDOXH
3.(VWZRUG
'ULYHREMHFW
,QGH[
$.
Figure 8-15
Telegram for a read request from p7841[2]
PNU (parameter number) and page index
Parameter number
PNU
Page index
0000 … 1999
0000 … 1999
0 hex
2000 … 3999
0000 … 1999
80 hex
6000 … 7999
0000 … 1999
90 hex
8000 … 9999
0000 … 1999
20 hex
10000 … 11999
0000 … 1999
A0 hex
20000 … 21999
0000 … 1999
50 hex
30000 … 31999
0000 … 1999
F0 hex
60000 … 61999
0000 … 1999
74 hex
Subindex
For indexed parameters, the parameter index is located in subindex as hexadecimal value.
PWE: Parameter value or connector
Parameter values or connectors can be located in the PWE.
Table 8-32
Parameter value or connector
PWE 1
PWE 2
Parameter value
Bit 15 … 0
Bit 15 … 8
Bit 7 … 0
0
0
8-bit value
0
16-bit value
32-bit value
Connector
Bit 15 … 0
Bit 15 … 10
Bit 9 … 0
Number of the connector
3F hex
The index or bit field
number of the connec‐
tor
Advanced commissioning
8.6 Drive control via PROFIBUS or PROFINET
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
201