Table 8-19
Set three-wire control, enable/clockwise/counterclockwise rotation in quick commissioning
Parameter
Description
p0015 = 19
Macro drive unit
Assigning digital inputs to the commands:
• Digital input 0: Enable/OFF1
• Digital input 1: ON clockwise rotation
• Digital input 2: ON counter-clockwise rotation
Wiring example for the factory settings (Page 80)
Parameter
Parameter
Description
Factory setting
r0722.0…n
CO/BO: CU digital inputs, status
-
p0840[C]
BI: ON/OFF (OFF1)
0
p1113[C]
BI: Setpoint inversion
0
p3330[C]
BI: 2/3 wire control command 1
0
p3331[C]
BI: 2/3 wire control command 2
0
p3332[C]
BI: 2/3 wire control command 3
0
r3333.0…n
CO/BO: 2/3 wire control control word
-
p3334
2/3 wire control selection
3: Three-wire control enable/clockwise/counterclockwise ro‐
tation
0
Advanced commissioning
8.5 Controlling clockwise and counter-clockwise rotation via digital inputs
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL