5. Select Assume control priority to establish the connection to the PG/PC. The Assume
control priority dialog is displayed.
Figure 6-18 Assuming control priority
6. Consider the following infeed options for the type of connection you are using.
– If you are using an infeed with a DRIVE-CLiQ interface, select the infeed for which the
control priority is to be assumed at Infeed in the Assume control priority dialog.
Activate the Infeed option if the infeed control priority is to be assumed and activated.
– If you are using an infeed without a DRIVE-CLiQ interface, you must interconnect the
Infeed operation signal (drive parameter p0864) yourself. In this case, the dialog does
not contain any fields for selecting infeed.
– If the signal of the Closed-loop control operation infeed is already BICO interconnected
with the drive, the infeed is specified permanently. No selection is possible in the dialog,
the fields are grayed out.
7. Observe the safety regulations and confirm with Accept.
The PG/PC has the control priority; the button caption has changed to Return control priority.
Note
You can also stop the drive at any time by pressing the SPACEBAR.
Configuring/parameterizing
6.4 Configuring devices
SIMOTION SCOUT
98
Configuration Manual, 11/2016