Tables, data records
3.4 Tables, PROFINET data records
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
239
Byte.Bit
Designation
Type
Range
Unit
Information
134.0
Reserved
136.0
Reserved
138.0
Reserved
140.0
Reserved
Byte[4]
144.0
Current I_max_F (float)
Float
1 A
UM+
148.0
Current I_avg_F
Float
1 A
UM+
152.0
Current I_L1_F
Float
1 A
UM+
156.0
Current I_L2_F
Float
1 A
UM+
160.0
Current I_L3_F
Float
1 A
UM+
164.0
Active power P_F
Float
1 W
UM+
168.0
Apparent power S_F
Float
1 VA
UM+
172.0
Voltage U1_F
Float
1 V
UM+
176.0
Voltage U2_F
Float
1 V
UM+
180.0
Voltage U3_F
Float
1 V
UM+
184.0
Cos phi_F
Float
UM+
188.0
Frequency_F
Float
1 Hz
UM+
192.0
Reserved
Byte[8]
1) S7 format:
0/4 mA = 0
20 mA = 27648
2) Representation of the "Thermal motor model":
Value always refers to symm. trip level,
representation in steps of 2% in bits 6 ... 0 (range 0 to 254%), bit 7 shows unbalance (fixed
level 50%).
3) Representation in Kelvin.
4) 3UF7510-1AA00-0 ground-fault module