Tables, data records
3.3 Tables, PROFIBUS data records
SIMOCODE pro - Communication
196
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
3.3.2.15
Data record 134 - Extended device parameters 2
Table 3- 37 Data record 134 - ExtendedPlus device parameters
Byte.Bit Designation (PRM group)
Type
Range
Unit
Default
Note
Info
Part - Bit[2] parameters
17.0
Internal ground fault+ -
Warning response
Bit[2]
0, 1, 2
0
0 = Disabled
1 = Signaling
2 = Warn
UM+
Part - Bit[4] parameters
22.4
Internal ground fault+ -
Hysteresis
Bit[4]
0 ... 15
1 %
5
UM+
Part - Byte parameters
42.0
Internal ground fault+ -
warning delay
Byte
0 ... 255
100 ms
1
UM+
Part - Word parameters
43.0
Internal ground fault+ - Trip
level
Word
10 ... 120
% / I_e
0
Value range
dependent on
current range of
the UM+
UM+
44.0
Internal ground fault+ -
Warning level
Word
10 ... 120
% / I_e
0
Value range
dependent on
current range of
the UM+
UM+
148
Part - Float parameters
172.0
Reserved
Float
3.3.2.16
Data record 135 - Extended device parameters 2
This data record is available for the SIMOCODE pro V PROFIBUS basic unit from
version V4.0 and the SIMOCODE pro V Modbus RTU basic unit from version V2.0.
The bytes of this data record that are not mentioned are reserved entries that are not used
by the stated devices.
Table 3- 38 Data record 135 - ExtendedPlus device parameters 2
Byte.Bit
Designation (PRM group)
Type
Range
Unit
Default
Note
Info
Part - FII byte parameters
100.0
PLC / PCS analog FI input
FII byte
0 ... 255
0
BU2+
101.0
PLC / PCS analog FI input
FII byte
0 ... 255
0
BU2+
102.0
PLC / PCS analog FI input
FII byte
0 ... 255
0
BU2+
103.0
PLC / PCS analog FI input
FII byte
0 ... 255
0
BU2+
107 ... 113
Reserved