Tables, data records
3.3 Tables, PROFIBUS data records
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
189
Byte.Bit Designation (PRM group)
Type
Range
Unit Default Note
Information
28.0
Bit[4] - Parameters (25)
28.0
TM - sensor type
Bit[3] +
Bit
000B to 100B
000B
000B = PT100
001B = PT1000
010B = KTY83
011B = KTY84
100B = NTC
TM1 MM
28.4
OPD - Language
Bit[4]
0 - 15
0
BU2+
29.0
External fault 5 - Reset also by
Bit[4]
0 - 1111B
0101B Bit[0] = Panel
reset
Bit[1] = Auto-
reset
Bit[2] = Remote
reset
Bit[3] = OFF
command reset
BU2(+)
29.4
External fault 6 - Reset also by
Bit[4]
0 - 1111B
0101B
BU2(+)
30.0
OPD - Contrast (bit 0 to 3)
Bit[4]
0 - 255
1 %
50
BU2+
30.4
OPD - Contrast (bit 4 to 7)
Bit[4]
BU2+
31.0
OPD - Profile (bit 0 to 3)
Bit[4]
0 - 33
0
BU2+
31.4
OPD - Profile (bit 4 to 7)
Bit[4]
BU2+
32.0
Truth table 7 type 2I/1O
Bit[4]
0 - 1111B
0
BU0 BU2(+)
32.4
Truth table 8 type 2I/1O
Bit[4]
0 - 1111B
0
BU0 BU2(+)
33.0
I
s
1 conversion factor - Denominator Bit[4]
0 - 15
0
BU2(+)
33.4
I
s
2 conversion factor - Denominator Bit[4]
0 - 15
0
BU2(+)
34.0
Hysteresis P - Cos phi - U
Bit[4]
0 - 15
5
1 %
UM(+)
34.4
Hysteresis 0/4-20 mA
Bit[4]
0 - 15
5
1 %
AM1
35.0
Hysteresis free limits
Bit[4]
0 - 15
5
1 %
BU2(+)
35.4
OPD - Lighting
Bit[4]
0 - 4
2
0 = Off
1 = 3 s
2 = 10 s
3 = 1 min
4 = 5 min
BU2+
36.0
Byte parameters (29)
36.0
Reserved
Byte
0
37.0
EM / MM - delay trip
Byte
0 - 255
100
ms
5
EM MM
38.0
Trip level cos phi<
Byte
0 - 100
1 % 0
UM(+)
39.0
Warning level cos phi<
Byte
0 - 100
1 % 0
UM(+)
40.0
Trip level U<
Byte
0 - 255
8 V
0
UM(+)
41.0
Warning level U<
Byte
0 - 255
8 V
0
UM(+)
42.0
Trip level 0/4-20 mA>
Byte
0 - 255
*128 0
AM1
43.0
Warning level 0/4-20 mA>
Byte
0 - 255
*128 0
AM1
44.0
Trip level 0/4-20 mA<
Byte
0 - 255
*128 0
AM1