Tables, data records
3.3 Tables, PROFIBUS data records
SIMOCODE pro - Communication
190
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Byte.Bit Designation (PRM group)
Type
Range
Unit Default Note
Information
45.0
Warning level 0/4-20 mA<
Byte
0 - 255
*128 0
AM1
46.0
Trip delay P>
Byte
0 - 255
100
ms
5
UM(+)
47.0
Warning delay P>
Byte
0 - 255
100
ms
5
UM(+)
48.0
Trip delay P<
Byte
0 - 255
100
ms
5
UM(+)
49.0
Warning delay P<
Byte
0 - 255
100
ms
5
UM(+)
50.0
Trip delay cos phi<
Byte
0 - 255
100
ms
5
UM(+)
51.0
Warning delay cos phi<
Byte
0 - 255
100
ms
5
UM(+)
52.0
Trip delay U<
Byte
0 - 255
100
ms
5
UM(+)
53.0
Warning delay U<
Byte
0 - 255
100
ms
5
UM(+)
54.0
Trip delay 0/4-20 mA>
Byte
0 - 255
100
ms
5
AM1
55.0
Warning delay 0/4-20 mA>
Byte
0 - 255
100
ms
5
AM1
56.0
Trip delay 0/4-20 mA<
Byte
0 - 255
100
ms
5
AM1
57.0
Warning delay 0/4-20 mA<
Byte
0 - 255
100
ms
5
AM1
58.0
Delay limit 1
Byte
0 - 255
100
ms
5
BU2(+)
59.0
Delay limit 2
Byte
0 - 255
100
ms
5
BU2(+)
60.0
Delay limit 3
Byte
0 - 255
100
ms
5
BU2(+)
61.0
Delay limit 4
Byte
0 - 255
100
ms
5
BU2(+)
62.0
TM - Hysteresis
Byte
0 - 255
1 K
5
TM1 MM
63.0
Max. star time
Byte
0 - 255
1 s
20
Star-delta starter BU0 BU2(+)
64.0
UVO time
Byte
0 - 255
100
ms
0
BU2(+)
65.0
Staggering time
Byte
0 - 255
1 s
0
BU2(+)
66.0
Analog value recording - Sampling
rate
Byte
0 - 20
5%
0
BU2(+)
67.0
Calculation module 2 -
Denominator 1
Byte
0 - 255
0
BU2(+)
68.0
Calculation module 2 - Numerator 2 Byte
0 - 255
0
BU2(+)
69.0
Calculation module 1 - Denominator Byte
0 - 255
0
BU2(+)
70.0
Truth table 4 type 3I/1O
Byte
0 -
11111111B
0
BU0,
BU2(+)