Tables, data records
3.5 Modbus data tables
SIMOCODE pro - Communication
304
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Input/holding register Designation
Type Range
Unit
Default Comments
Access
1)
Info
Address high/
low
Bit
0x4387
high
0-1
Reserved
Bit[2]
0
r
2-3
Reserved
Bit[2]
0
r
4-5
Reserved
Bit[2]
0
r
6-7 AM1 - active inputs Bit[2] 0, 1, 2
0
0 = 1 input
1 = 2 inputs
2 = 3 inputs
r
low
0-1 DM - Input delay
Bit[2] 0 ... 3
10
ms
1
Offset 6 ms
r
2-3 AM1 - Response to
open circuit
Bit[2] 1, 2, 3
2
0 = Disabled
1 = Signaling
2 = Warn
3 = Tripping
r
4-5 EM - response to an
external ground fault
Bit[2] 1, 3
1
r
6-7 EM - response to
warning of an
external ground fault
Bit[2] 0, 1, 2
0
r
0x4388
high 0-1
Reserved
Bit[2]
0
r
2-3
Reserved
Bit[2]
0
r
4-5 DM-F - Test
requirement
response
Bit[2] 0, 1, 2
0
r
6-7 DM-F - safety-
related tripping
response
Bit[2] 0, 1, 2, 3
0
r
low
0-1 TM1 - Trip
response T>
Bit[2] 1, 3
3
r
2-3 TM1 - Warning
response T>
Bit[2] 0, 1, 2
2
r
4-5 TM1 - Response to
a sensor fault / out
of range
Bit[2] 0, 1, 2, 3
2
r
6-7 TM1 - active sensors Bit[2] 0, 1, 2
2*)
0 = 1 sensors
1 = 2 sensors
2 = 3 sensors
r
0x4389 high 0-1 Trip response P>
Bit[2] 0, 1, 3
0
0 = Disabled
1 = Signaling
2 = Warn
3 = Tripping
r
2-3 Warning response
P>
Bit[2] 0, 1, 2
0
4-5 Trip response P<
Bit[2] 0, 1, 3
0
r
6-7 Warning response
P<
Bit[2] 0, 1, 2
0
r
low
0-1 Trip response
cos phi <
Bit[2] 0, 1, 3
0
r
2-3 Warning response
cos phi <
Bit[2] 0, 1, 2
0
r
4-5 Trip response U<
Bit[2] 0, 1, 3
0
r