Tables, data records
3.3 Tables, PROFIBUS data records
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
191
Byte.Bit Designation (PRM group)
Type
Range
Unit Default Note
Information
71.0
Truth table 5 type 3I/1O
Byte
0 -
11111111B
0
BU2(+)
72.0
Truth table 6 type 3I/1O
Byte
0 -
11111111B
0
BU2(+)
73.0
Calculation module 2 - Numerator 1 Byte
-128 - 127
0
BU2(+)
74.0
Calculation module 2 -
Denominator 2
Byte
-128 - 127
0
BU2(+)
75.0
DM-F - Test requirement level
Byte
0 - 255
1
week
0
BU2(+)
76.0
Word parameters (33)
76.0
Analog module - Start value output Word
0 - 65535
0
Value for 0/4mA AM1
78.0
Analog Module - End value output
Word
0 - 65535
27648 Value for 20mA
AM1
80.0
TM - Trip level T>
Word
0 - 65535
1 K
0
TM1 MM
82.0
TM - Warning level T>
Word
0 - 65535
1 K
0
TM1 MM
84.0
Limit monitor 1 - Limit
Word
0 - 65535
0
BU2(+)
86.0
Limit monitor 2 - Limit
Word
0 - 65535
0
BU2(+)
88.0
Limit monitor 3 - Limit
Word
0 - 65535
0
BU2(+)
90.0
Limit monitor 4 - Limit
Word
0 - 65535
0
BU2(+)
92.0
Timer 3 - Limit
Word
0 - 65535
100
ms
0
BU2(+)
94.0
Timer 4 - Limit
Word
0 - 65535
100
ms
0
BU2(+)
96.0
Counter 3 - Limit
Word
0 - 65535
0
BU2(+)
98.0
Counter 4 - Limit
Word
0 - 65535
0
BU2(+)
100.0
Change-over pause
Word
0 - 65535
10
ms
0
102.0
Analog value recording - Sampling
rate
Word
1 - 50000
1 ms 100
BU2(+)
104.0
I
s
1 conversion factor - Numerator
Word
0 - 65535
0
BU2(+)
106.0
I
s
2 conversion factor - Numerator
Word
0 - 65535
0
BU2(+)
108.0
D-word parameters (37)
108.0
Motor protection - Set current I
s
2
D-word
1)
10
mA
0
BU2(+)
112.0
Trip level P>
D-word 0 -
0xFFFFFFFF
1 W 0
UM(+)
116.0
Warning level P>
D-word 0 -
0xFFFFFFFF
1 W 0
UM(+)
120.0
Trip level P<
D-word 0 -
0xFFFFFFFF
1 W 0
UM(+)
124.0
Warning level P<
D-word 0 -
0xFFFFFFFF
1 W 0
UM(+)