Tables, data records
3.4 Tables, PROFINET data records
SIMOCODE pro - Communication
266
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Byte.Bit Designation (PRM group)
Type
Range
Unit
Default
Note
Info
29.0
Reserved
29.4
Reserved
30.0
Part - Byte parameters
30.0
Trip level 0/4-20 mA >
Byte
0 - 255
*128
0
AM2
31.0
Warning level 0/4-20 mA >
Byte
0 - 255
*128
0
AM2
32.0
Trip level 0/4-20 mA <
Byte
0 - 255
*128
0
AM2
33.0
Warning level 0/4-20 mA <
Byte
0 - 255
*128
0
AM2
34.0
Trip delay 0/4-20 mA >
Byte
0 - 255
100 ms
5
AM2
35.0
Warning delay 0/4-20 mA >
Byte
0 - 255
100 ms
5
AM2
36.0
Trip delay 0/4-20 mA <
Byte
0 - 255
100 ms
5
AM2
37.0
Warning delay 0/4-20 mA <
Byte
0 - 255
100 ms
5
AM2
38.0
Delay limit 5
Byte
0 - 255
100 ms
5
39.0
Delay limit 6
Byte
0 - 255
100 ms
5
40.0
Truth table 10 type 3I/1O
Byte
0 - 11111111B
0
41.0
Truth table 11 type 3I/1O
Byte
0 - 11111111B
0
Part - Byte parameters
42.0
Internal ground fault+ - warning
delay
Byte
0 ... 255
100 ms
1
UM+
43.0
Internal ground fault+ - Trip
level
Word
0 ... 65535
1 mA
0
Value range
dependent on
current range of
the UM+
UM+
44.0
Internal ground fault+ - Warning
level
Word
0 ... 65535
1 mA
0
Value range
dependent on
current range of
the UM+
UM+
45.0
TLS - delay
Byte
0 ... 100
100 ms
5
UM+_TL
46.0
TLS - T bridge
Byte
0 ... 120
500 ms
0
UM+_TL