Integrating SIMOCODE pro into the automation system (PLC)
I/O configurations
SIMOCODE pro V PN supports a number of I/O configurations which define the structure
and length of the I/O data that are cyclically exchanged between the EtherNet/IP
scanner (PLC) and the adapter (SIMOCODE pro). These configurations are referred to as
"basic types" and can be selected on the basis of the chosen assembly instances when the
device is integrated in Studio 5000.
The data that are exchanged with the EtherNet/IP scanner can be set by means of function
blocks such as, for example, "Cyclic receive byte 0" or "Cyclic send byte 0" in the
SIMOCODE ES software. Detailed information about the relationship between
SIMOCODE ES function blocks and assembly instances can be found in Chapter Assembly
object (Page 316).
Overview of the cyclic data available with SIMOCODE pro V EtherNet/IP:
Input data length
Input assembly
Output data length
Output assembly
Basic Type 1
10 byte
150
4 bytes
100
Basic Type 2
4 bytes
151
2 bytes
101
Basic Type 3
20 bytes
152
6 bytes
102
Basic Type 4
488 bytes
153
6 bytes
102