Tables, data records
3.3 Tables, PROFIBUS data records
SIMOCODE pro - Communication
170
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Byte.Bit Designation
Information
DP
diagnostics *)
Error No. **)
23.5
Fault - Bus
BU0 BU1 BU2(+)
5
23.6
Fault - PLC/PCS
BU0 BU1 BU2(+)
6
23.7
Reserved
24.0
Faults - Control
Fault - execution ON command BU1 BU2(+)
F
8
24.1
Fault - execution STOP
command
BU1 BU2(+)
F
9
24.2
Fault - feedback (FB) ON
BU1 BU2(+)
F
10
24.3
Fault - feedback (FB) OFF
BU1 BU2(+)
F
11
24.4
Fault - Stalled positioner
CF = positioner
F
12
24.5
Fault - Double 0
CF = positioner
F
13
24.6
Fault - Double 1
CF = positioner
F
14
24.7
Fault - End position
CF = positioner
F
15
25.0
Fault - Antivalence
CF = positioner
F
16
25.1
Fault - Cold start (TPF) fault
BU0 BU1 BU2(+)
F
17
25.2
Fault - power failure (UVO)
BU2(+)
F
18
25.3
Fault - Operational Protection
Off (OPO)
BU2(+)
F
19
25.4
Reserved
26.0
Reserved
26.1
Faults - Protection
Fault - unbalance
IM UM
F
25
26.2
Fault - overload
IM UM
F
26
26.3
Fault - ov phase failure IM UM
F
27
26.4
Fault - int. ground fault
IM UM
F
28
26.5
Fault - ext. ground fault
EM MM
F
29
26.6
Reserved
26.7
Fault - thermistor overload
Th
F
31
27.0
Fault - thermistor short circuit
Th
F
32
27.1
Fault - thermistor open circuit
Th
F
33
27.2
Reserved
27.3
Fault - TM trip T>
TM MM
F
35
27.4
Fault - TM sensor fault
TM MM
F
36
27.5
Fault - TM out of range
TM MM
F
37
27.6
Fault - EM+ open circuit
MM EM(+)
1)
F
27.7
Fault - EM+ short-circuit
MM EM(+)
1)
F
28.0
Faults - level
monitoring
Fault - trip I>
IM UM
F
40
28.1
Fault - trip I<
IM UM
F
41
28.2
Fault - trip P>
UM
F
42
28.3
Fault - trip P<
UM
F
43
28.4
Fault - trip cos phi<
UM
F
44
28.5
Fault - trip U<
UM
F
45
28.6
Fault - Trip 0/4 - 20mA>
AM
F
46