Tables, data records
3.5 Modbus data tables
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
295
Input/holding register
Designation
Type Range Unit Default Comments
Info
Access
1)
Address high/low Bit
0x4187 high
0
Motor protection -
Type of load
Bit
0, 1
0
0 = 3-phase
1 = 1-phase
r
1
Motor protection -
Reset
Bit
0, 1
0
0 = Manual
1 = Auto
r
2
Reserved
Bit
0
r
3
Save change-
over command
Bit
0, 1
0
r
4
Non-maintained
command mode
Bit
0, 1
0
r
5
Cold start level
(TPF)
Bit
0, 1
0
0 = NO contact
1 = NC contact
r
6
Type of
consumer load
Bit
0, 1
0
0 = Motor
1 = ohmic load
r
7
Reserved
Bit
0
r
low
0
External fault
level 1
Bit
0, 1
0
0 = NO contact
1 = NC contact
r
1
External fault
level 2
Bit
0, 1
0
r
2
External fault
level 3
Bit
0, 1
0
r
3
External fault
level 4
Bit
0, 1
0
r
4
Monitoring
external fault 1
Bit
0, 1
0
0 = Always
1 = Only motor ON
r
5
Monitoring
external fault 2
Bit
0, 1
0
r
6
Monitoring
external fault 3
Bit
0, 1
0
r
7
Monitoring
external fault 4
Bit
0, 1
0
r
Part - Bit[2]
parameter
0x4188 high
0-1
Thermistor -
Overload
response
Bit[2] 1, 2, 3
3
0 = Disabled
1 = Signaling
2 = Warn
3 = Tripping
r
2-3
Thermistor -
Response to
sensor fault
Bit[2] 0, 1, 2,
3
2
r
4-5
Internal ground
fault - Response
Bit[2] 0, 1, 2,
3
0
r
6-7
Motor protection -
Overload
response
Bit[2] 0, 1, 2,
3
0
r
low
0-1
Motor protection -
Overload
response
Bit[2] 0, 1, 2
2
r