Byte.Bit Designation
Information
PNIO
diagnostic
status **)
PNIO error
number (channel
error type)
Error no.
24.5
Fault - Double 0
CF =
positioner
3
0x1005
13
24.6
Fault - Double 1
CF =
positioner
3
0x1006
14
24.7
Fault - End position
CF =
positioner
3
0x1007
15
25.0
Fault - Antivalence
CF =
positioner
3
0x1008
16
25.1
Fault - Cold starting (TPF) fault
3
0x100A
17
25.2
Fault - UVO fault
3
0x100B
18
25.3
Fault - OPO fault
3
0x100C
19
25.4
Reserved bit[4]
26.0
Reserved
26.1
Fault -
Protection
Fault - Unbalance
IM UM(+)
3
0x1021
25
26.2
Fault - Overload
IM UM(+)
3
0x1022
26
26.3
Fault - Ov phase
failure
IM UM(+)
3
0x1023
27
26.4
Fault - Int. ground fault
IM UM(+)
3
0x1027
28
26.5
Fault - Ext. ground fault
EM
3
0x1028
29
26.6
Reserved
26.7
Fault - Thermistor overload
Th
3
0x1024
31
27.0
Fault - Thermistor short circuit Th
3
0x1025
32
27.1
Fault - Thermistor open circuit Th
3
0x1026
33
27.2
Reserved
27.3
Fault - TM1 trip T>
TM1
3
0x102B
35
27.4
Fault - TM1 sensor fault
TM1
3
0x102C
36
27.5
Fault - TM1 out of range
TM1
3
0x102D
37
27.6
Fault - EM+ open circuit
EM+
3
0x1029
27.7
Fault - EM+ short-circuit
EM+
3
0x102A
28.0
Faults - Level
monitoring
Fault - Trip I>
IM UM(+)
3
0x1040
40
28.1
Fault - Trip I<
IM UM(+)
3
0x1041
41
28.2
Fault - Trip P>
UM(+)
3
0x1042
42
28.3
Fault - Trip P<
UM(+)
3
0x1043
43
28.4
Fault - Trip cos phi<
UM(+)
3
0x1045
44
28.5
Fault - Trip U<
UM(+)
3
0x1047
45
28.6
Fault - Trip 0/4-20 mA>
AM1
3
0x1048
46
28.7
Fault - Trip 0/4-20 mA<
AM1
3
0x1049
47
29.0
Fault - Stalled rotor
IM UM(+)
3
0x104C
48
29.1
Reserved bit[3]
29.4
Fault - Number of starts >
3
0x1057
52