Tables, data records
3.5 Modbus data tables
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
285
Input/holding
register
Type Discrete
input / coil
address
Identifier
Access
1)
Address high/low
0x1C07
low
Bit
0x1C70
Event - startup parameter block active
r
0x1C71
Event - parameter changes not allowed in the current
operating state
r
0x1C72
Event - Device does not support the required functions
r
0x1C73
Event - Bad parameter
r
0x1C74
Event - Password wrong
r
0x1C75
Event - Password protection active
r
0x1C76
Event - Factory settings
r
0x1C77
Event - Parameterization active
r
high
Bit
0x1C78
Event - Prm error number
r
0x1C79
Event - Prm error number
r
0x1C7A
Event - Prm error number
r
0x1C7B
Event - Prm error number
r
0x1C7C
Event - Prm error number
r
0x1C7D
Event - Prm error number
r
0x1C7E
Event - Prm error number
r
0x1C7F
Event - Prm error number
r
0x1C08
low
Bit
0x1C80
Event - DM-FL configuration operation
r
0x1C81
Event - DM-FL actual and set configuration are different
r
0x1C82
Event - DM-FL waiting for start-up test
r
0x1C83
Reserved
r
0x1C84
Event - initialization module write-protected, parameter
changes not allowed
r
0x1C85
Event - memory module write-protected
r
0x1C86
Event - initialization module write-protected
r
0x1C87
Event - initialization module ident. data write protected
r
high
Bit
0x1C88
Warning - overload operation
r
0x1C89
Warning - Unbalance
r
0x1C8A
Warning - Overload
r
0x1C8B
Warning - Ov phase failure
r
0x1C8C
Warning - Internal ground fault
r
0x1C8D
Warning - external ground fault
r
0x1C8E
Reserved
r
0x1C8F
Warning - Thermistor overload
r
0x1C09
low
Bit
0x1C90
Warning - Thermistor short circuit
r
0x1C91
Warning - Thermistor open circuit
r
0x1C92
Warning - TM1 warning T >
r
0x1C93
Reserved
r
0x1C94
Warning - TM1 sensor fault
r
0x1C95
Warning - TM1 out of range
r
0x1C96
Warning - EM+ open circuit
r