Tables, data records
3.5 Modbus data tables
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
305
Input/holding register Designation
Type Range
Unit
Default Comments
Access
1)
Info
Address high/
low
Bit
6-7 Warning response
U<
Bit[2] 0, 1, 2
0
r
0x438A high 0-1 Trip response 0/
4-20 mA >
Bit[2] 0, 1, 3
0
r
2-3 Warning response
0/4-20 mA >
Bit[2] 0, 1, 2
0
r
4-5 Trip response 0/
4-20 mA <
Bit[2] 0, 1, 3
0
r
6-7 Warning response
0/4-20 mA <
Bit[2] 0, 1, 2
0
r
low
0-1
Reserved
Bit[2]
0
r
2-3
Reserved
Bit[2]
0
r
4-5
Reserved
Bit[2]
0
r
6-7
Reserved
Bit[2]
0
r
0x438B
high 0-1 External fault
response 5
Bit[2] 1, 2, 3
1
r
2-3 External fault
response 6
Bit[2] 1, 2, 3
1
r
4-5
Reserved
Bit[2]
0
r
6-7
Reserved
Bit[2]
0
r
low
0-1 Trace - Trigger edge Bit[2] 0, 1
0
0 = positive
1 = negative
r
2-3
Reserved
Bit[2]
0
r
4-5
Reserved
Bit[2]
0
r
6-7
Reserved
Bit[2]
0
r
0x438C high
0-1
Reserved
Bit[2]
0
r
2-3
Reserved
Bit[2]
0
r
4-5
Reserved
Bit[2]
0
r
6-7
Reserved
Bit[2]
0
r
low
0-1 Timer 3 - type
Bit[2] 0, 1, 2, 3
0
0 = With closing
delay
1 = Closing delay
with memory
2 = With OFF
delay
3 = With fleeting
closing
r
2-3 Timer 4 - type
Bit[2] 0, 1, 2, 3
0
r
4-5 Signal
conditioning 3 - type
Bit[2] 0, 1, 2, 3
0
0 = Non-inverting
1 = Inverting
2 = Edge rising
with memory
3 = Edge falling
r
6-7 Signal
conditioning 4 - type
Bit[2] 0, 1, 2, 3
0
r
0x438D high 0-1 Non-volatile
element 3 - type
Bit[2] 0, 1, 2, 3
0
r