Tables, data records
3.4 Tables, PROFINET data records
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
255
Byte.Bit
Designation (PRM group)
Type
Range
Unit
Default
Note
Info
21.2
Reserved
Bit[2]
0
21.4
Reserved
Bit[2]
0
21.6
Reserved
Bit[2]
0
22.0
External fault 5 – Response Bit[2]
1, 2, 3
1
0 = Disabled
1 = Signaling
2 = Warn
3 = Tripping
22.2
External fault 6 – Response Bit[2]
1, 2, 3
1
22.4
Reserved
Bit[2]
0
22.6
Reserved
Bit[2]
0
23.0
Analog-value recording -
Trigger edge
Bit[2]
0, 1
0
0 = positive
1 = negative
23.2
Reserved
Bit[2]
0
23.4
Reserved
Bit[2]
0
23.6
Reserved
Bit[2]
0
24.0
Reserved
Bit[2]
0
24.2
Reserved
Bit[2]
0
24.4
Reserved
Bit[2]
0
24.6
Reserved
Bit[2]
0
25.0
Timer 3 - Type
Bit[2]
0, 1, 2, 3
0
0 = With closing
delay
1 = Closing delay
with memory
2 = With opening
delay
3 = With fleeting
closing
25.2
Timer 4 - Type
Bit[2]
0, 1, 2, 3
0
25.4
Signal conditioning 3 - Type Bit[2]
0, 1, 2, 3
0
0 = Non-inverting
1 = Inverting
2 = Edge rising with
memory
3 = Edge falling with
memory
25.6
Signal conditioning 4 - Type Bit[2]
0, 1, 2, 3
0
26.0
Non-volatile element 3 -
Type
Bit[2]
0, 1, 2, 3
0
26.2
Non-volatile element 4 -
Type
Bit[2]
0, 1, 2, 3
0
26.4
Calculator 2, Operator
Bit[2]
0, 1, 2, 3
0
0 = +
1 = -
2 = *
3 = /
26.6
Reserved
Bit[2]
0
27.0
Reserved
Bit[2]
0
27.2
Reserved
Bit[2]
0
27.4
OPD - Operator panel
display (bit 0 to 1)
Bit[2]
0 - 4
2
0 = Manual
1 = 3 s
2 = 10 s
3 = 1 min
4 = 5 min
27.6
OPD - Operator panel
display (bit 2 to 3)
Bit[2]
0 - 4
2