Tables, data records
3.5 Modbus data tables
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
287
Input/holding
register
Type Discrete
input / coil
address
Identifier
Access
1)
Address high/low
0x1CBF
Reserved
r
0x1C0C
low
Bit
0x1CC0
Fault - execution ON command
r
0x1CC1
Fault - execution STOP command
r
0x1CC2
Fault - Feedback (FB) ON
r
0x1CC3
Fault - Feedback (FB) OFF
r
0x1CC4
Fault - Stalled positioner
r
0x1CC5
Fault - Double 0
r
0x1CC6
Fault - Double 1
r
0x1CC7
Fault - End position
r
high
Bit
0x1CC8
Fault - Antivalence
r
0x1CC9
Fault - Cold run (TPF) error
r
0x1CCA
Fault - power failure (UVO)
r
0x1CCB
Fault - Operational Protection Off (OPO)
r
0x1CCC
Reserved
r
0x1CCD
Reserved
r
0x1CCE
Reserved
r
0x1CCF
Reserved
r
0x1C0D
low
Bit
0x1CD0
Reserved
r
0x1CD1
Fault - unbalance
r
0x1CD2
Fault - overload
r
0x1CD3
Fault - ov phase failure
r
0x1CD4
Fault - int. ground fault
r
0x1CD5
Fault - ext. ground fault
r
0x1CD6
Reserved
r
0x1CD7
Fault - thermistor overload
r
high
Bit
0x1CD8
Fault - thermistor short circuit
r
0x1CD9
Fault - thermistor open circuit
r
0x1CDA
Reserved
r
0x1CDB
Trip - TM1 trip T>
r
0x1CDC
Trip - TM1 sensor fault
r
0x1CDD
Trip - TM1 out of range
r
0x1CDE
Fault - EM+ open circuit
r
0x1CDF
Fault - EM+ short circuit
r
0x1C0E
low
Bit
0x1CE0
Fault - trip I>
r
0x1CE1
Fault - trip I<
r
0x1CE2
Fault - trip P>
r
0x1CE3
Fault - trip P<
r
0x1CE4
Fault - trip cos phi<
r
0x1CE5
Fault - trip U<
r
0x1CE6
Fault - Trip 0/4 - 20mA>
r