Tables, data records
3.4 Tables, PROFINET data records
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
245
Byte.
Bit
Designation (PRM group)
Type Range
Unit
Default Note
Information
19.0 Monitoring the number of starts
- Response to overshoot
Bit[2] 0, 1, 2, 3
0
19.2 Monitoring the number of starts
- Response to prewarning
Bit[2] 0, 1, 2
0
19.4 Motor operating hours
monitoring - Response
Bit[2] 0, 1, 2
0
19.6 Motor stop time monitoring -
Response
Bit[2] 0, 1, 2
0
20.0 External fault 1 - Response
Bit[2] 1, 2, 3
1
20.2 External fault 2 - Response
Bit[2] 1, 2, 3
1
20.4 External fault 3 – Response
Bit[2] 1, 2, 3
1
20.6 External fault 4 - Response
Bit[2] 1, 2, 3
1
21.0
Reserved
Bit[2]
0
21.2 Basic unit - Debounce time
inputs
Bit[2] 0 - 3
10
ms
1
Offset 6 ms
21.4 Timer 1 - Type
Bit[2] 0, 1, 2, 3
0
0 = With closing delay,
1 = Closing delay with memory
2 = With opening delay
3 = With fleeting closing
21.6 Timer 2 - Type
Bit[2] 0, 1, 2, 3
0
22.0 Signal conditioning 1 - Type
Bit[2] 0, 1, 2, 3
0
0 = Non-inverting
1 = Inverting
2 = Edge rising with memory
3 = Edge falling with memory
22.2 Signal conditioning 2 - Type
Bit[2] 0, 1, 2, 3
0
22.4 Non-volatile element 1 - Type
Bit[2] 0, 1, 2, 3
0
22.6 Non-volatile element 2 - Type
Bit[2] 0, 1, 2, 3
0
23.0 EM+
2)
- monitoring
Bit[2] 0, 1, 2, 3
0
0 = on
1 = on+
2 = run
3 = run+
23.2 EM+
2)
- monitoring warning
Bit[2] 0, 1, 2, 3
0
23.4 EM - response to an external
ground fault
Bit[2] 1, 3
1
0 = Disabled
1 = Signaling
2 = Warn
3 = Tripping
23.6 EM - response to warning of an
external ground fault
Bit[2] 0, 1, 2
0
24.0 Bit[4] - Parameters (24)
24.0 External fault 1 - Reset also by Bit[4] 0 - 1111B
0101B Bit[0] = Panel reset
Bit[1] = Auto-reset
Bit[2] = Remote reset
Bit[4] = OFF command reset
24.4 External fault 2 - Reset also by Bit[4] 0 - 1111B
0101B
25.0 External fault 3 - Reset also by Bit[4] 0 - 1111B
0101B
25.4 External fault 4 - Reset also by Bit[4] 0 - 1111B
0101B
26.0 Limit monitor - Hysteresis for
limit monitoring
Bit[4] 0 - 15
1 %
5
26.4 EM+
2)
- hysteresis
Bit[4] 0 - 15
1 %
5
27.0 Parameter target version -
Part a
Bit[4]
0
27.4 Parameter target version -
Part b
Bit[4]
0