Tables, data records
3.5 Modbus data tables
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
279
3.5.2.3
Measured values
Table 3- 74 Measured values
Input/holding register
Designation
Type
Range
Unit
Access
5)
Info
Address offset high/low
0x0800
Reserved
Byte[2]
r
0x0801
Reserved
Byte[2]
r
0x0802
high
Thermal motor model
Byte
0 - 255
See
2)
r
low
Phase unbalance
Byte
0 - 100
1 %
r
0x0803
high
Cos phi
Byte
0 - 100
1 %
r
low
Reserved
Byte[1]
r
0x0804
Reserved
Byte[2]
r
0x0805
Reserved
Byte[2]
r
0x0806
Max. current I_max
Word
0 - 65535
1 % / I
s
r
0x0807
Current I_L1
Word
0 - 65535
1 % / I
s
r
0x0808
Current I_L2
Word
0 - 65535
1 % / I
s
r
0x0809
Current I_L3
Word
0 - 65535
1 % / I
s
r
0x080A
Last trip current
Word
0 - 65535
1 % / I
s
r
0x080B
Time to trip
Word
0 - 65535
100 ms
r
0x080C
Cooling down period
Word
0 - 65535
100 ms
r
0x080D
Voltage U_L1
Word
0 - 65535
1 V
r
0x080E
Voltage U_L2
Word
0 - 65535
1 V
r
0x080F
Voltage U_L3
Word
0 - 65535
1 V
r
0x0810
AM1 - output
Word
0 - 32767
See
1)
r
0x0811
AM1 - input 1
Word
0 - 32767
r
0x0812
AM1 - input 2
Word
0 - 32767
r
0x0813
Reserved
Word
0 - 32767
r
0x0814
TM1 - Temperature
Word
0 - 65535
1 K see
3)
r
0x0815
TM1 - temperature 1
Word
0 - 65535
r
0x0816
TM1 - temperature 2
Word
0 - 65535
r
0x0817
TM1 - temperature 3
Word
0 - 65535
r
0x0818
EM+
4)
- ground-fault current Word
0 - 65535
r
0x0819
EM+
4)
- last tripping current Word
0 - 65535
r
0x081A
Active power P
D-word 0 - 0xFFFFFFFF 1 W
r
0x081C
Apparent power S
D word 0 - 0xFFFFFFFF 1 VA
r
0x0842
Frequency
Word
0 - 65535
0.01 Hz
r
from E03
0x0848
Current I_max_A_F
Float
1 A
r
from E03
0x084A
Current I_avg_A_F
Float
1 A
r
from E03
0x084C
Current I_L1_A_F
Float
1 A
r
from E03
0x084E
Current I_L2_A_F
Float
1 A
r
from E03
0x0850
Current I_L3_A_F
Float
1 A
r
from E03
0x0852
Active power P_F
Float
1 W
r
from E03
0x0854
Apparent power S
Float
1 VA
r
from E03