Tables, data records
3.5 Modbus data tables
SIMOCODE pro - Communication
298
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Input/holding register
Designation
Type Range Unit Default Comments
Info
Access
1)
Address high/low Bit
0x4190
high
Motor protection -
Delay with
unbalance
Byte 0 ...
255
100
ms
5
IM UM
(+)
r/w
low
Interlocking time Byte 0 ...
255
1 s
0
r/w
0x4191
high
FB time
Byte 0 ...
255
100
ms
5
0 = Disabled
r/w
low
Trip level I>
Byte 0 ...
255
4 % /
I_s
0
IM UM
(+)
r/w
0x4192
high
Warning level I> Byte 0 ...
255
4 % /
I_s
0
IM UM
(+)
r/w
low
Trip level I<
Byte 0 ...
255
4 % /
I_s
0
IM UM
(+)
r/w
0x4193
high
Warning level I< Byte 0 ...
255
4 % /
I_s
0
IM UM
(+)
r/w
low
Stalled rotor level Byte 0 ...
255
4 % /
I_s
0
IM UM
(+)
r/w
0x4194
high
Trip delay I>
Byte 0 ...
255
100
ms
5
IM UM
(+)
r/w
low
Warning delay I> Byte 0 ...
255
100
ms
5
IM UM
(+)
r/w
0x4195
high
Trip delay I<
Byte 0 ...
255
100
ms
5
IM UM
(+)
r/w
low
Warning delay I< Byte 0 ...
255
100
ms
5
IM UM
(+)
r/w