Tables, data records
3.6 EtherNet/IP data tables
SIMOCODE pro - Communication
316
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
3.6.3
Message Router object
The Message Router object is defined by CIP. It does not possess any class or instance
attributes, but simply transfers explicit messages to the relevant objects.
3.6.4
Assembly object
The following information applies to the Assembly object of the SIMOCODE pro V
EtherNet/IP device:
●
Class code: 0x04
●
Class attributes: 1, 2, 3
●
Number of instances: 13.
Instance 2: Output assembly basic overload from ODVA Profile
The tables below describe in each case the format of attribute 3 of the relevant assembly
instance.
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Reserved
Reserved
Reserved
Reserved
Reserved
Fault Reset Reserved
Reserved
Instance 50: Input assembly basic overload from ODVA Profile
The table below describes the format of attribute 3:
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved Faulted / Trip
Instance 51: Input assembly extended overload from ODVA Profile
The table below describes the format of attribute 3:
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Warning Faulted / Trip