Communication
2.2 PROFINET communication
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
87
Example:
The motor is to be switched on and off via the control station "PC/OPC UA."
OPC UA - Acyclic receive - Bit 0.0
→ Motor ON<
OPC UA - Acyclic receive - Bit 0.1
→ Motor OFF
OPC UA - Acyclic receive - Bit 0.2
→ Motor ON>
Figure 2-25 Example of OPC UA motor control
Note
Write access
Write access is only possible if a secure connection is used with Security policy
"Basic128Rsa15" and with Message security mode "SignAndEncrypt."
Note
Non-maintained command mode
Do not use the "non-maintained command mode" for motor control with OPC UA!