A5E00158716-02
Actuator selection data
Output voltage
•
at signal 1
min. 2L+ (– 0.8 V)
Output current
•
at signal 1
Rated value
Permitted range
2 A
5 mA to 2.4 A
•
at ”0” signal (residual
current)
Max. 0.5 mA
Resistive load range
12
Ω
to 4 k
Ω
Lamp load
max. 10 W
Parallel connection of
two outputs
•
for load control
redundancy
possible
•
for power increase
No
Digital input control
possible
Switching frequency
•
resistive load
max. 100 Hz
•
inductive load
according to IEC
947-5-1, DC13
max. 0.5 Hz
•
lamp load
max. 1 Hz
Limiting (internal) of
inductive cut–off voltage
to
typically 2L+ (– 44 V)
Short–circuit protection of
outputs
•
response threshold
Yes, electronic
typically 4 A per
channel
6.8
I/O module 8 DI / 8 DO 1.3 A
(6ES7 143-3BH00-0XA0)
Properties
The I/O module 8 DI / 8 DO 1.3 A has the following features:
•
8 digital inputs
•
Input nominal voltage DC 24 V
•
suitable for switches and proximity switches (BEROs)
•
8 digital outputs
•
output current = 1,3 A per output
•
rated load voltage = 24 VDC
•
suitable for magnetic solenoid valves, DC contactors and signal lamps
Pin assignment of the DI sockets
The table below shows the pin assignment of the eight digital input and output
sockets.
Summary of Contents for SIMATIC ET 200eco
Page 8: ...Preface viii ET 200eco Distributed I O Station A5E00158716 02 ...
Page 18: ...Product overview 1 6 ET 200eco Distributed I O Station A5E00158716 02 ...
Page 70: ...Commissioning and diagnostics 4 16 ET 200eco Distributed I O Station A5E00158716 02 ...
Page 116: ...I O address area C 6 ET 200eco Distributed I O Station A5E00158716 02 ...
Page 124: ...Index Index 4 ET 200eco Distributed I O Station A5E00158716 02 ...