Commissioning and diagnostics
4-2
ET 200eco Distributed I/O Station
A5E00158716-02
4.1
ET 200eco configuration
GSD file
Configure the ET 200eco distributed I/O station via the GSD file. In this GSD file,
the ET 200eco is implemented as standard slave in your system. You can
download the GSD files
•
under the Internet URL http//www.ad.siemens.de/csi_e/gsd
GSD filenames for ET 200eco:
•
I/O module 8 DI: Siem80db.gs*
•
I/O module 16 DI: Siem80da.gs*
•
I/O module 8 DO 2 A: Siem80dd.gs*
•
I/O module 16 DO 0.5 A: Siem80fb.gs*
•
I/O module 8 DI / 8 DO 2 A: Siem80dc.gs*
•
I/Omodule 8 DI / 8 DO-2 1.3 A: Siem80fc.gs*
*
Placeholder for the corresponding language (e.g. German: Siem80db.gsg)
How to implement the GSD file in the configuration software
Table 4-1 below describes how to implement the GSD file in SIMATIC S7 or
SIMATIC S5 (COM PROFIBUS) systems.
Table 4-1
GSD file Implementation in the configuration software
Step
STEP 7, as of V4.02
COM PROFIBUS, V3.0 and higher
1
1
Start STEP 7. Open HW Config and
call menu command Extras
"
Install
new GSD file.
Copy the device database (GSD) file for
the ET 200eco to the COM PROFIBUS
directory: ...COMPB3\GSD (default
setting)
Copy the bitmap file to directory:
...COMPB3\BITMAPS
2
In the next dialog block, select the
GSD file you want to install and
confirm with OK.
Result: The field device is displayed
in the hardware catalog, under the
PROFIBUS–DP directory.
Start COM PROFIBUS. Select menu
command File
"
Load GSD file. Result:
ET 200eco is displayed in the hardware
catalog during slave configuration.
3
Configure ET 200eco under STEP 7
(See Integrated Help in STEP 7).
Configure ET 200eco under COM
PROFIBUS (See Integrated Help in COM
PROFIBUS).
1
Other configuration software: refer to the corresponding documentation
Summary of Contents for SIMATIC ET 200eco
Page 8: ...Preface viii ET 200eco Distributed I O Station A5E00158716 02 ...
Page 18: ...Product overview 1 6 ET 200eco Distributed I O Station A5E00158716 02 ...
Page 70: ...Commissioning and diagnostics 4 16 ET 200eco Distributed I O Station A5E00158716 02 ...
Page 116: ...I O address area C 6 ET 200eco Distributed I O Station A5E00158716 02 ...