Technical data
6-21
ET 200eco Distributed I/O Station
A5E00158716-02
Technical Data of the I/O Module 8 DI / 8 DO 2A
Dimensions and weight
Dimensions
W
H
D (mm)
60
210
28
Weight
approx. 210 g
Module–specific data
Transmission rates
9.6/19.2/45.45/93.75/
187.5/500 kbps
1.5/3/6/12 Mbps
Bus protocol
PROFIBUS-DP
Number of channels
8 digital outputs
Cable length
•
Unshielded
max. 30m
Manufacturer ID
80DC
H
Voltages, currents, potentials
Rated voltage of the
electronic/sensor power
supply 1L+
24 VDC
•
Reverse polarity
protection
no
Rated load voltage 2L+
24 VDC
•
Reverse polarity
protection
no
Number of inputs that can
be addressed
simultaneously
8
•
all mounting positions
up to 55
C
Cumulative current of the
outputs
•
all mounting positions
up to 55
C
each 4 A
1), 2)
Isolated potential
•
between channels
no
•
between PROFIBUS
DP and other circuit
components
yes
Permitted potential
difference
•
between different
circuits
75 VDC, 60 VAC
Isolation test voltage
500 VDC
Current load
•
on power supply 1L+
•
on load voltage supply
2L+
typically 70 mA
typically 60 mA
Power loss of the module
typically 5 W
Status, interrupts, diagnostics
Status display
Green LED per
channel
Interrupts
no
Diagnostic functions
•
Group error display
Red LED (SF)
•
Channel error display
no
•
Read access to
diagnostics data
possible
Encoder power supply outputs
Number of outputs
8
Output current
up to 55
C max.
0,75A (cumulative
current)
Short–circuit protection
yes, electronic
Encoder selection data
Input voltage
•
Rated value
•
for ”1” signal
•
for ”0” signal
24 VDC
13 to 30 V
– 3 to 5 V
Input current
•
at signal 1
•
at signal 0
typically 7 mA
Input delay
•
“0” to “1” transition
•
“1” to “0” transition
typically 3 ms
typically 3 ms
Input characteristic curve
according to IEC
61131, Type 1
Connection of 2–wire
BERO
possible
•
permitted no–load
current
max. 1.5 mA
1)
4 A cumulative current for sockets X1, X3, X5,
and X7; 4 A cumulative current for sockets X2,
X4, X6, and X8.
2)
Please note the current capacity of the cable
Summary of Contents for SIMATIC ET 200eco
Page 8: ...Preface viii ET 200eco Distributed I O Station A5E00158716 02 ...
Page 18: ...Product overview 1 6 ET 200eco Distributed I O Station A5E00158716 02 ...
Page 70: ...Commissioning and diagnostics 4 16 ET 200eco Distributed I O Station A5E00158716 02 ...
Page 116: ...I O address area C 6 ET 200eco Distributed I O Station A5E00158716 02 ...
Page 124: ...Index Index 4 ET 200eco Distributed I O Station A5E00158716 02 ...