General technical data
5-5
ET 200eco Distributed I/O Station
A5E00158716-02
5.3
Mechanical and climatic ambient conditions
Climatic ambient conditions
The following climatic ambient conditions apply:
Ambient conditions
Fields of application
Remarks
Temperature range
0 to 55
C
all mounting positions
Temperature change
10 K/h
Relative humidity
15 to max. 95 %
without condensation
Atmospheric pressure
1080 to 795 hPa
Proportional to an altitude of
-1000 to 2000 m
Contaminant concentration
SO
2
: < 0.5 ppm;
relative humidity < 60 %, no dewing
H
2
S: < 0.1 ppm;
relative humidity < 60 %, no dewing
Test:
10 ppm; 4 days
1 ppm; 4 days
Mechanical ambient conditions
The sine–wave diagrams in the table below specify mechanical ambient conditions.
Frequency
range
Continuous
test at ...
10
f
58 Hz
0.35 mm amplitude
0.75 mm amplitude
58
f
150 Hz
5 g constant acceleration
10 g constant acceleration