Technical data
6-10
ET 200eco Distributed I/O Station
A5E00158716-02
6.4
I/O module 16 DI (6ES7 141-3BH00-0XA0)
Properties
Characteristics of I/O module 16 DI:
•
16 digital inputs
•
Input nominal voltage DC 24 V
•
suitable for switches and proximity switches (BEROs)
Pin assignment of the DI sockets
The table below shows the pin assignment of the eight digital input sockets.
Table 6-5
Pin-out of the digital input sockets X1 to X8
Pin
Assignment of
socket X1
Assignment of
socket X2
Assignment of
socket X3
Assignment of
socket X4
View of the
socket (Front
view)
1
24 V sensor power supply
2
Input signal
channel 8
Input signal
channel 9
Input signal
channel 10
Input signal
channel 11
2
3
Ground potential of the sensor power supply
1
2
3
5
4
Input signal
channel 0
Input signal
channel 1
Input signal
channel 2
Input signal
channel 3
1
3
4
5
5
PE
Pin
Assignment of
socket X5
Assignment of
socket X6
Assignment of
socket X7
Assignment of
socket X8
1
24 V sensor power supply
2
Input signal
channel 12
Input signal
channel 13
Input signal
channel 14
Input signal
channel 15
3
Ground potential of the sensor power supply
4
Input signal
channel 4
Input signal
channel 5
Input signal
channel 6
Input signal
channel 7
5
PE
Summary of Contents for SIMATIC ET 200eco
Page 8: ...Preface viii ET 200eco Distributed I O Station A5E00158716 02 ...
Page 18: ...Product overview 1 6 ET 200eco Distributed I O Station A5E00158716 02 ...
Page 70: ...Commissioning and diagnostics 4 16 ET 200eco Distributed I O Station A5E00158716 02 ...
Page 116: ...I O address area C 6 ET 200eco Distributed I O Station A5E00158716 02 ...
Page 124: ...Index Index 4 ET 200eco Distributed I O Station A5E00158716 02 ...