General technical data
5-3
ET 200eco Distributed I/O Station
A5E00158716-02
5.2
EMC compatibility, shipping and storage conditions
Definition
EMC compatibility refers to the ability of electrical equipment to operate efficiently
in an electromagnetic environment, without emission of electromagnetic
disturbance.
The ET 200eco distributed I/O station is also compliant with EMC legislation of the
European common market. Prerequisite is here that the electrical installation of the
ET 200eco distributed I/O station is compliant with corresponding regulations and
guidelines.
Disturbance spikes
The table below shows EMC compatibility of the ET 200eco distributed I/O station
with reference to disturbance spikes.
Disturbance spikes
Tested with
corresponding
severity
Electrostatic discharge
according to IEC 61000-4-2.
8 kV
6 kV
3 (air discharge)
2 (contact discharge)
Burst pulses (fast transient disturbance va-
riables) according to
IEC 61000-4-4.
2 kV (power supply
line)
2 kV (signal line)
3
3
High–energy surge pulse according to IEC 61000-4-5
Applies only to lightning protection elements
(see the DP master manual and the description of SIMATIC NET
PROFIBUS Networks)
•
asymmetrical coupling
2 kV (power supply
line)
2 kV (signal/data
line)
3
•
symmetrical coupling
1 kV (power supply
line)
1 kV (signal/data
line)
Summary of Contents for SIMATIC ET 200eco
Page 8: ...Preface viii ET 200eco Distributed I O Station A5E00158716 02 ...
Page 18: ...Product overview 1 6 ET 200eco Distributed I O Station A5E00158716 02 ...
Page 70: ...Commissioning and diagnostics 4 16 ET 200eco Distributed I O Station A5E00158716 02 ...
Page 116: ...I O address area C 6 ET 200eco Distributed I O Station A5E00158716 02 ...
Page 124: ...Index Index 4 ET 200eco Distributed I O Station A5E00158716 02 ...