Pin assignment of the M12-, 7/8” sockets
The table below shows the pin assignment of the two M12, 7/8” sockets for the
connection to the power supplies and PROFIBUS DP.
Table 6-2
Pin-out of the plugs DP1 and DP2 (M12)
Pin
Assignment of the M12 sockets DP1
(infeed) and DP2 (loop–through)
(PROFIBUS DP)
View of the plug
(Front view of the terminal blocks)
1
Power (P5V2)
Supply DP1
Through–loop DP2
2
Data line A (RxD / TxD-N)
Supply DP1
Through–loop DP2
3
Data reference potential (M5V2)
1
2
5
1
2
4
Data line B (RxD / TxD-P)
3
4
5
3
4
5
5
Shielding
Thread
Shielding
Pin
Socket
Table 6-3
Pin-out of the connectors X01 and X02 (7/8”)
Pin
Pin out of the 7/8” sockets X01
(infeed) and X02 (loop–through)
(PROFIBUS-DP)
View of the plug
(Front view of the terminal blocks)
1
Ground potential, load voltage supply
(2M)
Supply
X01
Through–loop
X02
2
Ground potential, electronic/sensor
power supply (1M)
1
5
1
5
X01
X02
3
PE
2 3 4
2
3
4
4
Electronic/sensor power supply (1L+)
Pi
Socke
5
Load voltage supply (2L+)
Pi
n
Socke
t
Summary of Contents for SIMATIC ET 200eco
Page 8: ...Preface viii ET 200eco Distributed I O Station A5E00158716 02 ...
Page 18: ...Product overview 1 6 ET 200eco Distributed I O Station A5E00158716 02 ...
Page 70: ...Commissioning and diagnostics 4 16 ET 200eco Distributed I O Station A5E00158716 02 ...
Page 116: ...I O address area C 6 ET 200eco Distributed I O Station A5E00158716 02 ...
Page 124: ...Index Index 4 ET 200eco Distributed I O Station A5E00158716 02 ...