Installation
2-8
ET 200eco Distributed I/O Station
A5E00158716-02
How to set the PROFIBUS-DP address at the ECOFAST terminal block
Valid range of the PROFIBUS DP addresses: 1 to 99. If you select a higher
address, the I/O module will return an error signal via the red bus error LED.
1. Unscrew and remove the configuration module from the ECOFAST terminal
block.
1
Figure 2-5
How to unscrew the configuration module
2. Unscrew and remove the cap of the configuration module.
3. Set the PROFIBUS address on the DIL switches.
Example: PROFIBUS address 92
2
2
+ 2
3
+ 2
4
+ 2
6
= 4 + 8 + 16 + 64 = 92
ON
ON
1
7
2
3
4
5
6
2
Figure 2-6
How to set the PROFIBUS address at the configuration module
4. Screw on the cap again. Reinsert the configuration module and fasten it on the
terminal block with the screws.