Commissioning and diagnostics
4-4
ET 200eco Distributed I/O Station
A5E00158716-02
ET 200eco startup
LED “BF” is switched off; the in-
puts/outputs are enabled;
ET 200eco and the DP master
are ready to exchange data
Switch off 1L+ for ET 200eco
Switch on 1L+ and, if required,
2L+ for ET 200eco
yes
No
ET 200eco sets the outputs to
“0” state and applies the set
PROFIBUS address
ET 200eco receives configur–
ation data from the DP master
Are the
configuration data com-
patible to the physical
configuration?
Adapt the configuration data to
your system or vice versa
The LEDs “ON”,“24 VDC”
and “BF” are lit*
SF is lit red
BF flashes red
* The “24 VDC” LED is not available for I/O module 8 DI or I/O module 16 DI
Figure 4-1
ET 200eco startup