Wiring
3-19
ET 200eco Distributed I/O Station
A5E00158716-02
3.4.3
How to wire the ECOFAST terminal block
Properties
•
Connect the supply voltages and PROFIBUS DP to the ECOFAST terminal
block via ECOFAST connector.
•
You can loop the supply voltages and PROFIBUS DP through an additional
ECOFAST connector.
•
Always terminate the first and the last ET 200eco (node) on the PROFIBUS-DP
with a terminating resistor.
Requirements
You have set the PROFIBUS address (according to your project configuration).
Tools required
Screwdriver, wire stripper and crimp tool for wiring the ECOFAST connector – if
you are not using a ready–made ECOFAST connector.
Accessories required
•
ECOFAST hybrid prefabricated cable with ECOFAST plug. The cable is
available in various lengths.
•
If you do not use an ECOFAST hybrid prefabricated cable (see Table 3-11):
– Han Brid Cu plug or Han Brid Cu terminal box
– ECOFAST hybrid cable
•
Terminating resistor (ECOFAST) for PROFIBUS DP
•