Wiring
3-7
ET 200eco Distributed I/O Station
A5E00158716-02
Note
The following applies to an ET 200eco with terminal block:
•
The electronic/sensor power supply 1L+ powers the sensors.
•
The outputs are powered via by the load voltage supply 2L+.
Protecting components from damage
In order to avoid the destruction of ET200eco components, you must always
provide external line fusing for the electronic/sensor power supply and load
voltage:
•
Fusing of the electronic/sensor power supply (1L+):
DC 24 V / 10 A: Tripping characteristics (type) B or C
•
Fusing of the load voltage supply: (2L+) 24 VDC / 16 A:
Tripping characteristics (type) B or C
3.4
Wiring ET 200eco
In this
chapter,
you will find
on page
3.4.1
How to connect ET 200eco to protective earth (PE)
3.4.2
How to wire I/O modules
3.4.3
How to wire the ECOFAST terminal block
3.4.4
How to wire the M12, 7/8” terminal block
3.4.5
How to loop the PROFIBUS DP and the supply voltage
Wiring procedure
The ET 200eco distributed I/O station is wired in several steps. We recommend
you take the following procedure:
1. Connect ET 200eco to protective earth. See Chapter 3.4.1
2. Wire the I/O module. See Chapter 3.4.2
3. Wiring the terminal block. See Chapter 3.4.3, 3.4.4 or 3.4.5
Summary of Contents for SIMATIC ET 200eco
Page 8: ...Preface viii ET 200eco Distributed I O Station A5E00158716 02 ...
Page 18: ...Product overview 1 6 ET 200eco Distributed I O Station A5E00158716 02 ...
Page 70: ...Commissioning and diagnostics 4 16 ET 200eco Distributed I O Station A5E00158716 02 ...
Page 116: ...I O address area C 6 ET 200eco Distributed I O Station A5E00158716 02 ...
Page 124: ...Index Index 4 ET 200eco Distributed I O Station A5E00158716 02 ...