Technical data
6-26
ET 200eco Distributed I/O Station
A5E00158716-02
Actuator selection data
Output voltage
•
at signal 1
min. 2L+ (– 1.2 V)
Output current
•
at signal 1
Rated value
Permitted range
1.3 A
5 mA to 1.8 A
•
at ”0” signal (residual
current)
Max. 0.5 mA
Resistive load range
12
Ω
to 4 k
Ω
Lamp load
max. 10 W
Parallel connection of
two outputs
•
for load control
redundancy
possible
•
for power increase
No
Digital input control
possible
Switching frequency
•
resistive load
max. 100 Hz
•
inductive load
according to IEC
947-5-1, DC13
max. 0.5 Hz
•
lamp load
max. 1 Hz
Limiting (internal) of
inductive cut–off voltage
to
typically 2L+ (– 44 V)
Short–circuit protection of
outputs
•
response threshold
Yes, electronic
typically 4 A per
channel