General technical data
5-4
ET 200eco Distributed I/O Station
A5E00158716-02
Sinusoidal disturbance variables
The table below shows the EMC compatibility of the ET 200eco distributed I/O
station in relation to sinusoidal disturbances.
RF coupling toIEC 6100043
Electromagnetic RF field
RF coupling to
IEC 61000
amplitude–modulated
pulse–modulated
80 to 1000 MHz
900 MHz
5 MHz
0.15 to 80 MHz
10 V/m
10 V
r.m.s.
, unmodulated
80 % AM (1 kHz)
50 % ED
80 % AM (1 kHz)
200 Hz repetitive frequency
150
W
Source impedance
Emission of RF interference
Emitted electromagnetic interference to EN 55011: Limit value class A, Group 1
(measured at a distance of 10 m).
Frequency
Emitted interference
from 30 to 230 MHz
< 40 dB (
m
V/m)Q
from 230 to 1000 MHz
< 47 dB (
m
V/m)Q
Shipping and storage conditions
The shipping and storage conditions for the ET 200eco distributed I/O station
exceed IEC 61131-2 requirements. The specifications below apply to modules
stored or shipped in their original packaging.
Type of condition
Permitted range
Drop test
1 m
Temperature
– 40
C to + 70
C
Temperature change
20 K/h
Atmospheric pressure
1080 to 660 hPa (proportional to an altitude
of -1000 to 3500 m)
Relative humidity
5 to 95 %, without condensation
Summary of Contents for SIMATIC ET 200eco
Page 8: ...Preface viii ET 200eco Distributed I O Station A5E00158716 02 ...
Page 18: ...Product overview 1 6 ET 200eco Distributed I O Station A5E00158716 02 ...
Page 70: ...Commissioning and diagnostics 4 16 ET 200eco Distributed I O Station A5E00158716 02 ...
Page 116: ...I O address area C 6 ET 200eco Distributed I O Station A5E00158716 02 ...
Page 124: ...Index Index 4 ET 200eco Distributed I O Station A5E00158716 02 ...