Wiring
3-12
ET 200eco Distributed I/O Station
A5E00158716-02
•
I/O module 8 DI / 8 DO 2 A
Table 3-5
Pin assignment of M12 coupler plug for I/O module
8 DI / 8 DO 2 A
Pin
Assignment
View of the coupler plug
(wiring side)
1
24V sensor power supply (1L+)*
4- or 5–pole copper cable
2
Input signal
3
Ground potential, sensor/load voltage
supply (1M / 2M )**
1
2
3
5
4
Output signal
4
5
PE
*
sensor power supply via ET 200eco
** common ground potential for sensor/load voltage supply (1M and 2M internally
interconnected)