Commissioning and diagnostics
4-15
ET 200eco Distributed I/O Station
A5E00158716-02
4.4.6
Device–specific diagnostic data
Definition
Device–specific diagnostic data allows you to recognize a short–circuit at the
electronic/sensor power supply (1L+) or missing load voltage supply (2L+). The
header contains information on the length of device–specific diagnostic data.
Device–specific diagnostic data
Structure of device–specific diagnostic data for ET 200eco:
Byte 6
7
0
Bit no.
Length of device–specific diagnostics data,
including byte 6 (= 7 bytes)
Byte 7
1: missing load voltage supply (2L+)
Code for device–specific diagnostic data
0 0 0 0 0 1 1 1
7 6 5 4
1
3
Bit no.
0
1: short–circuit at the electronic/sensor power supply (1L+)
0 0 0 0 0 0
2
Figure 4-4
Structure of ET 200eco device–specific diagnostics data