W
ATER S
YSTEMS
Features
• 6 speed fan
• Cabinet factory fitted
• Valve factory fitted
• Electrical heater factory fitted
• Thermal or modulating valve
• Service valve
Dimensions indicated next page
(1) Cooling capacities based on 7ºC EWT
∆
t 5ºC indoor temperature 27ºC DB / 19ºC WB - (2 pipes - high speed fan)
(2) Heating capacities based on 70ºC EWT
∆
t 10ºC indoor temperature 20ºC - (2 pipes - high speed fan)
(3) In cooling mode 2 rows
For other conditions contact York international
Technical features
YLVR - YLIVR
Model
110
112
114
216
218
Cooling capacity (1) 2 rows
W
832
1054
1493
2041
2356
Cooling capacity (1) 3 rows
W
913
1266
1790
2327
2714
Heating capacity (2) 1 row
W
1167
1691
2319
3029
3552
Pressure drop (3)
kPa
7
1.7
3.8
9
11.7
Power supply
V/Ph/Hz
230 / 1 / 50 + E
Sound power level (3)
dB(A)
49
50
53
53
55
Sound pressure level at 3 m
dB(A)
31
32
35
35
37
Water connections
inch
1/2 “
Thermostats
CSL00 (Built in)
CSR00 (Wall mounted)
Fan speed selector
CML00 (Built in)
CMR00 (Wall mounted)
Thermostat with manual fan speed and S/W
change over
CEL00 (Built in)
CER00 (Wall mounted)
Thermostat with manual fan speed and automatic
change over
CEL20 (Built in)
CER20 (Wall mounted)
Thermostat with auto. fan speed and automatic
change over
CEL30 (Built in)
CER30 (Wall mounted)
Thermostat with auto. fan speed and automatic
change over for modulating valve
Fan Coil Unit
LOW BODY
(2 & 4 pipe system)
A complete range from 0.8 kW up to 2.7 kW
Selection
software