Commissioning and diagnostics
4-13
ET 200eco Distributed I/O Station
A5E00158716-02
Station status 2
Table 4-8
Structure of station status 2 (byte 1) ET 200eco
Bit
Meaning
0
1: The DP slave must be reconfigured.
1
1: A diagnostic message is queued. The DP slave will not operate unless
the error is eliminated (static diagnostic message).
2
1: The bit is always ”1” on the DP slave.
3
1: The watchdog is activated for this DP slave.
4
1: The DP slave has received a ”FREEZE” control command.*
5
1: The DP slave has received a ”SYNC” control command.
6
0: The bit is always ”0”.
7
1: When the station status is being read from the DP master, the bit is “1” if
the DP slave has been disabled in the DP master.
The DP slave is disabled; in other words, it is isolated from the current
process.
*
When the control command “FREEZE” is set, the diagnostic messages are also frozen.
Station Status 3
Table 4-9
Structure of station status 3 (byte 2) ET 200eco
Bit
Meaning
0 to 7
0: The bits are always ”0”.