INSTRUCTION MANUAL

RTD INPUT MODULE, 4 points

(DeviceNet)

MODEL

R7D-RS4

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

RTD input module ...............................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

 

EDS FILE

EDS files are downloadable at M-System’s web site: https://
www.m-system.co.jp

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• The equipment must be mounted inside the instrument 

panel of a metal enclosure.

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure the CE conform-
ity.

 

GENERAL PRECAUTIONS

• Before you remove the unit or mount it, turn off the power 

supply and input signal for safety.

• Before you remove the terminal block or mount it, make 

sure to turn off the power supply and input signal for 
safety.

• DO NOT set the switches on the module while the power 

is supplied.  The switches are used only for maintenance 
without the power.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C 

(14 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

• Be sure to close the terminal cover for safety.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

Summary of Contents for R7D-RS4

Page 1: ...have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE conform ity GENERAL PRECAUTIONS Before you remove the unit or mount it turn...

Page 2: ...2 500 kbps 3 thr 9 Auto tracking The R7D communicates in the baud rate setting detected at the startup with the switch set to the positions 0 125 kbps 1 250 kbps or 2 500 kbps For the settings 3 thro...

Page 3: ...7 sec 1 0 sec Status Data ON Disable OFF Enable OFF Enable Serial ID English one byte characters within 8 characters CHANNEL INDIVIDUAL SETTING PARAMETER SETTING RANGE DEFAULT SETTING RTD Type Pt 100...

Page 4: ...0 11 12 13 2 3 4 1 15 16 17 18 7 8 9 6 14 5 2 3 4 1 5 30 1 18 5 20 3 12 3 12 5 5 22 DIN RAIL 35mm wide 54 2 13 17 66 50 1 97 18 5 73 115 4 53 18 M3 SCREW TERMINALS for INPUT 6 24 TERMINAL BLOCK for De...

Page 5: ...e R7D EA16 with Status Analog Input Module CH0 CH1 CH2 CH3 Begin 0 1 2 3 Output Data Analog Input Module Status CH0 CH1 CH2 Begin 0 Begin 0 1 2 CH3 3 4 Output Data Input Data None Example 1 Analog Inp...

Page 6: ...PUT DATA 2 R7D to Master Master to R7D R7D RS4 4 0 EXTENSION MODULE Transmitted data word for the extension module is added MODEL OUTPUT DATA 1 INPUT DATA 2 R7D to Master Master to R7D R7D EAx 1 0 R7D...

Page 7: ...ng the R7D Make sure to adequately ground the control panel and the internal panel plate with a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out o...

Page 8: ...using an electro magnetically shielded control panel By connecting the internal panel plate and the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the con...

Page 9: ...ment Additional measures may be taken depending upon actual installation sites These points of cautions are illustrated in the next page Keep cables as short as possible It prevents noise emissions fr...

Page 10: ...ween cables and noise sources Grounding in pig tail form is not effective Points of cautions applicable when wiring the R7D Series To external apparatus Keep the cable as short as possible To external...

Reviews: