DETAILED CASE AND MODULE DESCRIPTION
_________________________________________________________________________________________________________
8-38
SIG-00-22-02 JUNE 2022 (Revised September 2022)
Version: B.1
NOTE
Effective with Revision D of the SSCC IIIi, FLASH SYNC is an isolated
two-wire output.
If two Revision D or later SSCC IIIi units in the same chassis are
operated by separate batteries, the FLASH SYNC returns are connected
internally and no additional connection is required.
Revision D SSCC IIIi Modules can be identified by either a “D” located at
end of the Part Number / Bar Code tag or by the large metal bracket
located on the component side of the module.
When external SSCC units are connected to a master SSCC IIIi and
operated from a different battery, the following wiring must be provided
for FLASH SYNC Return:
If an external SSCC IIIA, SSCC III PLUS, or SSCC IV is connected to a
master SSCC IIIi:
If the SSCC IIIi is Revision D or later, the SSCC IIIi FLASH SYNC return
(-) must be connected to N on the external SSCC.
The terminology for flash sync control differs between a GCP5000 (GCE)
and an external SSCC device. The GCP5000 (GCE) terms Master and
Slave SSCC, are called “Flash Sync Out” and “Flash Sync In”
respectively in an external SSCC (Slave = Flash Sync In)