DISPLAY MODULE AND OFFICE CONFIGURATION EDITOR
_________________________________________________________________________________________________________
3-44
SIG-00-22-02 JUNE 2022 (Revised September 2022)
Version: B.1
11. Scroll down to select the file to be installed, in this example 9VC72-V3H00_02.010.
Select
Enter
.
12. The new MEF begins loading. This may take a few minutes. While the file is uploading,
progress will be indicated on the bottom line of the window.
13. When complete, the Display text provides all of the module update options. Select
0)
Exit Setup
.
14. The Upload to System window opens and states:
Exit software finished rebooting the
module
.
Figure 3-67 Exit Software
15. Press the
Back
button.
3.4.2.4 Replace VLP MEF on CPU III via WebUI
1. Locate the IP address of the GCP5000 unit via the selector buttons on the front of the
CPU III unit. Type https:// or http:// (depending on the method selected in the Web
Server Configuration) followed by the IP address
2. Login to the WebUI using the appropriate User Name and Password.